Main line ABB UL listed circuit breaker for overload protection
Shunt Trip on MLCB
MLCB Auxiliary Contacts
Starter battery/ies installed (cables and bracket included)
Battery charger (Optional)
10 Amp battery charger, 12/24V DC, UL Listed (Optional)
Control Panel Heater (Optional)
- EXHAUST SYSTEM.
Maximum exhaust temperature: 950 ºF
Exhaust Gas Flow: 19,211 cfm
Maximum allowed back pressure: 600 mm H2o
- NECESSARY AMOUNT OF AIR.
Intake air flow: 7,243 scfm
Alternator fan air flow: 7,310 scfm
- STARTING SYSTEM.
Starting power: 7.5 x 2 kW
Starting power: 10.06 x 2 HP
Recommended battery: 300 Ah
Auxiliary Voltage: 24 Vdc
- FUEL SYSTEM
Fuel Oil Specifications: Diesel
Maximum power suction pump: 75 mm Hg
Maximum return feed pump: 150 mm Hg
Dimensions
- DIMENSIONS.
Length: 235 in
Height: 120 in
Width: 95 in
Maximum shipping volume: 1550.31 ft3
Weight with liquids in radiator and sump: 37,000 Lbs
Power Equipment Built Around Your Timeline
WPP keeps a large inventory of power generation equipment and supports customers with practical guidance from selection through delivery.
Whether you are replacing aging equipment, sourcing for a project, or coordinating a larger power package, our team helps you find the right fit and move forward with confidence.
Large Equipment Inventory
New, used, and refurbished generators, engines, and accessories.
Project-Ready Support
Help with sizing, submittals, equipment matching, and coordination.
One-Stop Shop
Sales, rental, service, and parts support under one roof.