Hurricane Milton Alert: For generator, cable, and power distribution rental and sales inquiries, visit our Emergency Response Page.

  • Inc 500 Honoree
  • America's 100 Most Promising Companies

NFPA 110 Emergency Generator Testing Requirements

The National Fire Protection Association (NFPA) establishes safety standards that protect commercial building occupants against various dangers.   NFPA 110 covers performance requirements for emergency and standby power systems providing an alternate source of electrical power in buildings and facilities in the event that the normal electrical power source fails.

Systems include power sources, transfer equipment, controls, supervisory equipment, and accessory equipment needed to supply electrical power to the selected circuits.

NFPA logo

Generator maintenance
Technician setting up remote generator monitoring
CAT generator undergoing load bank test

MONTHLY TESTING

A monthly test is performed on Level 1 and Level 2 generators. A Level 1 generator is one whose failure could result in death or serious injury. A level 2 generator is one whose failure would not result in life-threatening injury. During testing, a generator should operate under available load for a minimum of thirty minutes. A successful test is one in which the generator:

  • Achieves the minimum exhaust gas temperature for monthly testing as indicated by the owners manual, or
  • Operates at normal temperature while running at no less than 30% of the nameplate Kilowatt rating.

If a generator cannot operate until its water and oil pressures have stabilized, it should be tested for less than thirty minutes to avoid prolonging its down time.

Transfer switches shall be operated monthly. (8.4.6) The monthly test of a transfer switch shall consist of electrically operating the transfer switch from the primary position to the alternate position and then a return to the primary position. Note: Although it is not required to verify the type rating of the system during the monthly test, it is required to annually confirm that the system responds within the time dictated by its rating.

EPSS circuit breakers for Level 1 system usage, including main and feed breakers between the EPS and the transfer switch load terminals, shall be exercised annually with the EPS in the “off” position. (8.4.7) Circuit breakers rated in excess of 600 volts for Level 1 system usage shall be exercised every 6 months and shall be tested under simulated overload conditions every 2 years. Note: It is not intended that the circuit breakers be exercised under load.

EPSS components shall be maintained and tested by qualified person(s). (8.4.8)

YEARLY TESTING (Sec.  8.2.4.3)

If a generator fails the monthly test, it should be operated under a load supplied by a load bank (i.e. load bank testing) for two continuous hours each year. During this two-hour period, the unit should be operated as follows:

  • At 25% of the nameplate Kilowatt rating for 30 minutes.
  • At 50% of the nameplate Kilowatt rating for 30 minutes.
  • At 75% of the nameplate Kilowatt rating for 60 minutes.

The “exercise” supplied by load bank testing can improve a generator’s operating capacity, making it more responsive during a real power outage.

RECORDKEEPING

Records shall be created and maintained for all EPSS inspections, operational tests, exercising, repairs, and modifications. (8.5.1)

The record shall include the following: (8.5.3)

  1. The date of the maintenance report
  2. Identification of the servicing personnel
  3. Notation of any unsatisfactory condition and the corrective action taken, including parts replaced
  4. Testing of any repair in the time recommended by the manufacturer

This new section was created in the 2016 edition to consolidate record. No retention time is specified to reflect actual operating conditions. However, the retention period may be defined by the facility management or the authority having jurisdiction (AHJ) and must be made available to the AHJ on request.

MANUALS, SPECIAL TOOLS AND SPARE PARTS

At least two sets of instruction manuals for all major components of the EPSS shall be supplied by the manufacturer. These manuals should contain detailed explanations of the operations and maintenance tasks, an illustrated parts list with part numbers, and schematic diagrams of electrical wiring systems (one-line drawings), including operating and safety devices, control panels, instrumentation, and annunciators. (8.2.1)

For Level 1 systems, instruction manuals shall be kept in a secure, convenient location, one set near the equipment, and the other set in a separate location. (8.2.2)

Special tools and testing devices necessary for routine maintenance shall be available when needed. (8.2.3)

Spare parts as recommended by the manufacturer or by experience should be stocked and maintained in a secure location on the premises. (8.2.4)

It is recommended that the instruction manuals, special tools, and spare parts be stored in a metal cabinet in the generator room. The instruction manual should be stored on the inside of the cabinet door.

ROUTINE MAINTENANCE AND OPERATIONAL TESTING

Chapter 8 of NFPA 110 contains requirements for performing maintenance on Emergency Power Supply Systems (EPSSs). Planned maintenance is a critical part of any backup power system. Regular verification that an installed system is functional is necessary to ensure that standby power will be available when called upon at a loss of primary power.

All components of the system, from fuel quality up to the operation of the transfer switch, are addressed in this chapter because each relies on the other. These operational testing requirements are the minimum benchmarks for proper operation of the EPSS.

NFPA 110 requires that the manufacturer’s maintenance recommendations be followed along with the instruction manuals, the minimum requirements of this chapter, and any additional requirements of the authority having jurisdiction (AHJ).  (8.1.1) Random inspection and testing are not a basis for maintaining the dependability of an EPSS. The continued reliability of the EPSS is dependent on an established program of routine maintenance and operational testing.

It also requires that consideration be given to temporarily providing a portable generator or alternate source of emergency power whenever the emergency generator is out of service or during routine testing. (8.1.2).

© 2024 Worldwide Power Products